Estimate peak runoff using the Rational Method. Designed for SuDS designers, drainage engineers, and local authority officers.

Q = CiA
Q  — peak runoff rate (litres / second) C  — runoff coefficient (surface type) i   — rainfall intensity (mm / hr) A  — catchment area (m²)
Catchment area
Surface type

Runoff coefficient: C = 0.90

Rainfall intensity

Adjusted intensity: 60.0 mm/hr (50.0 base × 1.20)

mm/hr
Peak runoff — Rational Method
— litres / second
peak flow rate at the catchment outlet

— m³/s   ·   — m³/hr
Estimation only. The Rational Method is suitable for small catchments (typically under 80 ha) and uniform surfaces. For mixed surfaces, calculate each zone separately and sum. Rainfall intensities shown are UK typicals — obtain site-specific values from the Environment Agency's Flood Estimation Handbook (FEH) or UKCP18 data for formal design. Always verify with hydraulic modelling before submission to a planning or adoption authority.

About the Rational Method

The Rational Method (Q = CiA) is the standard approach for estimating peak runoff from small catchments. It is widely used in UK drainage practice for SuDS feasibility assessments, public realm design, and planning-stage drainage strategies.

The method assumes uniform rainfall intensity across the catchment, a consistent surface type, and steady-state conditions. For larger or more complex catchments — particularly those above 80 ha, or with significant storage — hydraulic modelling tools such as HEC-HMS, Micro Drainage, or InfoDrainage are more appropriate.

A desktop calculation gives you a starting point. Understanding the real drainage behaviour of a site — soil permeability, hidden drainage assets, micro-topography, and actual surface conditions — requires a site visit. See how our Desktop Study + Site Visit works.

Need infiltration-based sizing for a roof or small catchment? Use our Rain Garden Calculator, or talk to us about SuDS design for a complete, buildable drainage scheme.

Runoff coefficient (C) values by surface type

The runoff coefficient is usually the single biggest influence on the result — it sets how much rainfall becomes surface runoff rather than soaking in. These are typical UK design values. For a site with more than one surface, calculate each zone separately or use an area-weighted average C, and always check against CIRIA C753 (The SuDS Manual) or your lead local flood authority's guidance for formal design.

Surface typeRunoff coefficient (C)
Impermeable paving / tarmac0.90
Rooftop / flat roof0.85
Gravel / permeable paving0.45
Lawn / grass0.25
Woodland / meadow0.10

Worked example: a car park drainage check

A developer needs the peak runoff from a 1,200 m² asphalt car park for a 1-in-30-year storm, with a climate change allowance.

  • Area (A) = 1,200 m²
  • Surface = impermeable asphalt → C = 0.90
  • Rainfall = 50 mm/hr base (1-in-30-year) + 20% climate allowance → i = 60 mm/hr

Applying Q = CiA and converting to litres per second:

Q = 0.90 × 60 × 1,200 ÷ 3,600 = 18 litres/second

That is 0.018 m³/s, or 64.8 m³/hr — the peak flow the drainage or SuDS scheme must manage. Enter the same figures above to reproduce this result.

Frequently asked questions

How do you calculate surface water runoff?

Use the Rational Method, Q = CiA: multiply the runoff coefficient (C), the rainfall intensity (i, in mm/hr) and the catchment area (A, in m²), then divide by 3,600 to get the peak flow in litres per second.

What does the runoff coefficient (C) represent?

C is the fraction of rainfall that becomes surface runoff rather than soaking in or being intercepted. It ranges from about 0.10 for woodland to 0.90 and above for tarmac and roofs — see the table above.

Does this tool give the greenfield runoff rate?

Not directly. Greenfield runoff is the rate a site discharged before development, and it is the benchmark most planning authorities hold new development to. It is normally estimated with the IH124 or FEH methods rather than the Rational Method, which is best suited here to the developed, impermeable case.

Rational Method or Modified Rational Method — which applies?

The standard method gives peak flow only. The Modified Rational Method, used in UK sewer design, also estimates runoff volume and hydrograph shape by accounting for storm duration — which matters when sizing attenuation storage.

Which rainfall intensity should I use?

For a quick check, the return-period presets above give UK-typical values. For formal design, obtain site-specific intensities from the Environment Agency's FEH data or UKCP18, and apply the climate change allowance appropriate to your planning horizon.

When should you not use the Rational Method?

It is intended for small, fairly uniform catchments (typically under 80 ha). For large or complex catchments, significant on-site storage, or formal flood modelling, use hydraulic tools such as InfoDrainage, Micro Drainage or HEC-HMS — and always validate before submission to a planning or adoption authority.

Related tools & next steps